Commercial Water Leaks Detection - Landsdale
Fire Main Piping
Westscan’s water leak detection service locates water leaks on fire mains using tracer gas.
A non-compliance issue needed rectifying on a commercial strata complex under construction in Landsdale, Perth, WA. The fire main piping and hose reel piping were installed by two separate contractors. When pressure testing was conducted on the fire main, it was found not to be holding pressure. Westscan used ground penetrating radar to locate the route of the fire main piping. Once the piping route was confirmed, tracer gas injection was initiated. Where pressure loss is of small volume at high pressure, tracer gas is an excellent tool.
The water leak / pressure loss was found to be on a loose-fitting end cap on the pre-laid fire hose reel red line poly piping. Repair work only required the fitting to be properly tightened.


Site – Strata Complex
Site owner – Commercial building company
Location – Landsdale, Western Australia
Scope – Water leak detection on the fire main piping
Project – New Construction Non-compliance – identify location of pressure/water loss
Landsdale is in the local government area of Wanneroo, in the northern suburbs of Perth.